Overview Used in W7080 control system to provide modulating space temperature control. Features Separate heat and cool adjustable set point levers provide adjustable deadband from 3 F to 30 F (2 C to 17 C).Single 2 to 22 Vdc voltage ramp provides heating/cooling signal to W7080 Load Analyzer.Outputs constant 12 Vdc when sensed temperature is within deadband range.Ramp output decreases on call for heat: increases on call for cooling.C7100B or C7046B Air Temperature Sensors are used to provide heating/cooling anticipation (one required for each zone thermostat) and can also be optionally used as remote return air temperature sensors with the T7080B transmitter.Operates on 24 Vdc supplied by W7080A Load Analyzer.Mounts on standard 2 x 4 in. outlet box or on nonconductive flat surface.
Application Size :
3 Heat / 3 Cool
Control System :
W7080 control system
Output Type :
Voltage Ramp
Voltage :
24 Vdc
Setpoint Temperature Range (C) :
13 C to 29 C
Setpoint Temperature Range (F) :
55 F to 85 F
Shipping and Storage Temperature Range (F) :
-40 F to +150 F
Shipping and Storage Temperature Range (C) :
-40 C to +65 C
Approvals, Department of Defense Guidelines :
Meets
Approvals, ASHRAE Guidelines :
Meets ASHRAE 90-75