EasyLogic PM2220, Power & Energy meter, up to 15th H, LCD, RS485, class 1
- [Us] rated supply voltage : 44...277 V AC 45...65 Hz +/- 10 %~~
- [Us] rated supply voltage : 44...277 V DC +/- 10 %
- Accuracy Class : Class 1 active energy IEC 62053-21
- Accuracy Class : Class 1 reactive energy IEC 62053-24
- Accuracy Class : Class 5 harmonic distortion (I THD & U THD)
- Ambient Air Temperature For Operation : 14…140 °F (-10…60 °C)
- Analogue Input Type : Current (impedance
- Analogue Input Type : Voltage (impedance > 5 MOhm)
- Application : Power monitoring
- Application : Sub billing
- Brand : Schneider Electric
- By Schneider : Yes
- Carbon footprint (kg CO2 eq, Total Life cycle) : 129
- Communication Port Protocol : Modbus RTU 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires 2500 V
- Communication Port Support : Screw terminal block RS485
- Communication Service : Remote monitoring
- Connections - Terminals : Current transformer screw connection bottom) 6
- Connections - Terminals : Voltage inputs screw connection top) 4
- Control Type : 4 x button
- cybersecurity : Enable/disable communication ports
- Data Recording : Min/max for 8 parameters
- Data Recording : Time stamping
- Depth : Embedded : 2.43 in (61.64 mm)
- Depth : Total : 3.00 in (76.09 mm)
- Device Short Name : PM2220
- Display Colour : Monochrome
- Display Resolution : 128 x 128 pixels
- Display Type : Backlit LCD
- Electromagnetic Compatibility : Conducted RF disturbances conforming to IEC 61000-4-6
- Electromagnetic Compatibility : Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
- Electromagnetic Compatibility : Electrostatic discharge conforming to IEC 61000-4-2
- Electromagnetic Compatibility : Emission tests conforming to FCC part 15 class A
- Electromagnetic Compatibility : Magnetic field at power frequency conforming to IEC 61000-4-8
- Electromagnetic Compatibility : Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
- Electromagnetic Compatibility : Surge immunity test conforming to IEC 61000-4-5
- Electromagnetic Compatibility : Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
- Final Result for Connectable : Connectable ready
- Final Result for Flywheel performance tracking : Connectable products
- Flame Retardance : V-0 conforming to UL 94
- Frequency Measurement Range : 45…65 Hz
- Function Available : Real time clock
- Global Keywords : Class 1 accuracy
- Global Keywords : EasyLogic
- Global Keywords : Energy
- Global Keywords : Flush-mount energy meter
- Global Keywords : LCD display
- Global Keywords : PM2000
- Global Keywords : Power
- Global Keywords : RS485
- Global warming ; Total life cycle? : 129 kg CO2 eq.
- Height : 3.8 in (96 mm)
- Indivisible Sale Qty : 1
- Information Displayed : Active power
- Information Displayed : Apparent power
- Information Displayed : Current
- Information Displayed : Demand current past value)
- Information Displayed : Demand current present value)
- Information Displayed : Demand power past value)
- Information Displayed : Demand power present value)
- Information Displayed : Energy consumption
- Information Displayed : Frequency
- Information Displayed : Harmonic amplitude
- Information Displayed : Harmonic distortion
- Information Displayed : Power factor
- Information Displayed : Reactive power
- Information Displayed : Unbalanced in %
- Information Displayed : Voltage
- Insulation Class : Class II
- Insulation Class : Double insulation
- IP Degree of Protection : IP30 body: conforming to IEC 60529
- IP Degree of Protection : IP54 front: conforming to IEC 60529
- Language : Chinese
- Language : English
- Language : French
- Language : German
- Language : Portuguese
- Language : Russian
- Language : Spanish
- Line Rated Current : 1 A
- Line Rated Current : 5 A
- Local Signalling : Green LED module operation and integrated communication
- Local Signalling : Red LED output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
- Manufacturer : Schneider Electric
- Material : Polycarbonate
- Maximum Power Consumption In Va : 6 VA 277 V AC
- Maximum Power Consumption In W : 2 W 277 V power lines (DC))
- Maximum Power Consumption In W : 3.3 W power lines (AC))
- Measurement Accuracy : Active energy +/- 1 %
- Measurement Accuracy : Active power +/- 1 %
- Measurement Accuracy : Apparent power +/- 1 %
- Measurement Accuracy : Current +/- 0.5 %
- Measurement Accuracy : Frequency +/- 0.05 %
- Measurement Accuracy : Power factor +/- 0.01
- Measurement Accuracy : Reactive energy +/- 1 %
- Measurement Accuracy : Voltage +/- 0.5 %
- measurement category : Category II 480…600 V
- measurement category : Category III 480 V
- Measurement Current : 5…6000 mA
- Measurement Voltage : 20…277 V AC 50/60 Hz between phase and neutral
- Measurement Voltage : 35…480 V AC 50/60 Hz between phases
- Measurement Voltage : 480…999000 V AC 50/60 Hz with external VT
- Metering Type : Active power P, P1, P2, P3
- Metering Type : Active, reactive, apparent energy (signed, four quadrant)
- Metering Type : Apparent power S, S1, S2, S3
- Metering Type : Calculated neutral current
- Metering Type : Current I, I1, I2, I3
- Metering Type : Demand power P, Q, S
- Metering Type : Peak demand currents
- Metering Type : Peak demand power PM, QM, SM
- Metering Type : Reactive power Q, Q1, Q2, Q3
- Metering Type : Unbalance current
- Metering Type : Voltage U, U21, U32, U13, V, V1, V2, V3
- Mounting Mode : Clip-on
- mounting position : Vertical
- Mounting Support : Framework
- Net Weight : 10.6 oz (300 g)
- Network Frequency : 50 Hz
- Network Frequency : 60 Hz
- Number Of Inputs : 0
- Number Of Outputs : 0
- Number of Units in Package 2 : 18
- Number of Units in Package 3 : 144
- Overvoltage Category : III
- Package 2 GTIN : 43606480800175
- Package 2 Height : 11.81 in (30.000 cm)
- Package 2 Length : 15.75 in (40.000 cm)
- Package 2 Weight : 15.459 lb(US) (7.012 kg)
- Package 2 width : 11.81 in (30.000 cm)
- Package 3 Height : 29.53 in (75.000 cm)
- Package 3 Length : 31.50 in (80.000 cm)
- Package 3 Weight : 171.961 lb(US) (78.000 kg)
- Package 3 width : 23.62 in (60.000 cm)
- Packaging made with recycled cardboard : Yes
- Packaging without single use plastic : No
- Pollution Degree : 2
- Power Quality Analysis : total harmonic distortion
- Power Quality Analysis : up to the 15th harmonic
- Product Certifications : CE conforming to IEC 61010-1
- Product Certifications : C-tick
- Product Certifications : CULus conforming to CSA C22.2 No 61010-1
- Product Certifications : CULus conforming to UL 61010-1
- Product Certifications : EAC
- Product Certifications : RCM
- Product Name : EasyLogic PM2200
- Product Or Component Type : Power meter
- Provided Equipment : 1 x Installation guide
- Range : EasyLogic
- refresh time : Configurable from 1 to 60 min
- Relative Humidity : 5…95 % 122 °F (50 °C)
- Ride-Through Time : 100 ms 120 V AC typical
- Ride-Through Time : 400 ms 230 V AC typical
- Ride-Through Time : 50 ms 125 V DC typical
- Sampling Rate : 64 samples/cycle
- SCIP Number : 6599793e-9401-4187-a617-35919522fe23
- Service Life : 7 year(s)
- Take-back : No
- Tamperproof Of Settings : Protected by access code
- Temperature Shipping and Storage Range : -13…158 °F (-25…70 °C)
- Type Of Measurement : Active and reactive energy total
- Type Of Measurement : Active and reactive power min/max, total
- Type Of Measurement : Apparent energy total
- Type Of Measurement : Apparent power min/max, total
- Type Of Measurement : Current min/max, avg
- Type Of Measurement : Frequency min/max, avg
- Type Of Measurement : Power factor min/max, avg
- Type Of Measurement : Total current harmonic distortion THD (I) per phase
- Type Of Measurement : Total voltage harmonic distortion THD (U) per phase
- Type Of Measurement : Voltage min/max, avg
- Unit Type of Package 2 : S03
- Unit Type of Package 3 : P06
- UNSPSC Classification v19 : 41113708
- UNSPSC Classification v23 : 41113708
- Volume of Package 2 : 36000.000 cm3
- Volume of Package 3 : 360000.000 cm3
- Width : 3.8 in (96 mm)