TeSys D Contactor |Number of Poles: 3-Poles|Pole Contact Composition: 3 NO|Rated Operational Current: 18A|Control Circuit Voltage: 120V AC 50/60 Hz|Reversing
[Icw] rated short-time withstand current :
100 A - 1 s for signalling circuit~~
[Icw] rated short-time withstand current :
120 A - 500 ms for signalling circuit
[Icw] rated short-time withstand current :
140 A - 100 ms for signalling circuit
[Icw] rated short-time withstand current :
145 A 104 °F (40 °C) - 10 s for power circuit
[Icw] rated short-time withstand current :
240 A 104 °F (40 °C) - 1 s for power circuit
[Icw] rated short-time withstand current :
40 A 104 °F (40 °C) - 10 min for power circuit
[Icw] rated short-time withstand current :
84 A 104 °F (40 °C) - 1 min for power circuit
[Ie] rated operational current :
18 A (at
[Ie] rated operational current :
32 A (at
[Ith] conventional free air thermal current :
10 A (at 140 °F (60 °C)) for signalling circuit
[Ith] conventional free air thermal current :
32 A (at 140 °F (60 °C)) for power circuit
[Uc] control circuit voltage :
120 V AC 50/60 Hz
[Ue] rated operational voltage :
Power circuit
[Ui] rated insulation voltage :
Power circuit 600 V CSA
[Ui] rated insulation voltage :
Power circuit 600 V UL
[Ui] rated insulation voltage :
Power circuit 690 V IEC 60947-4-1
[Ui] rated insulation voltage :
Signalling circuit 600 V CSA
[Ui] rated insulation voltage :
Signalling circuit 600 V UL
[Ui] rated insulation voltage :
Signalling circuit 690 V IEC 60947-1
[Uimp] rated impulse withstand voltage :
6 kV IEC 60947
Associated Fuse Rating :
35 A gG at
Associated Fuse Rating :
50 A gG at
auxiliary contact composition :
1 NO + 1 NC
auxiliary contacts type :
Mirror contact 1 NC IEC 60947-4-1
By Schneider :
Yes
Carbon footprint (kg CO2 eq, Total Life cycle) :
42
climatic withstand :
IACS E10
climatic withstand :
IEC 60947-1 Annex Q category D
contact compatibility :
M2
contactor application :
Motor control
contactor application :
Resistive load
control circuit type :
AC 50/60 Hz
Depth :
3.4 in (86 mm)
Device Short Name :
LC2D
Electrical Durability :
1 Mcycles 32 A AC-1
Electrical Durability :
1.65 Mcycles 18 A AC-3
Final Result for Flywheel performance tracking :
Non Flywheel
Flame Retardance :
V1 conforming to UL 94
Global Keywords :
3-pole reversing contactor
Global Keywords :
AC coil
Global Keywords :
AC-3
Global Keywords :
Built-in auxiliary contact
Global Keywords :
LC2D
Global Keywords :
Mechanical interlock
Global Keywords :
Motor control
Global Keywords :
Motor switching
Global Keywords :
Pre-wired connections
Global Keywords :
Reversing contactor
Global Keywords :
Reversing power contactor
Global Keywords :
Screw clamp terminals
Global Keywords :
TeSys D
Global warming ; Total life cycle? :
42 kg CO2 eq.
Heat Dissipation :
2…3 W 50/60 Hz
Height :
3.03 in (77 mm)
insulation resistance :
> 10 MOhm for signalling circuit
interlocking type :
Mechanical
IP Degree of Protection :
IP20 front face IEC 60529
Manufacturer :
Schneider Electric
Maximum Horse Power Rating :
1 hp at 115 V AC 60 Hz for 1 phase motors
Maximum Horse Power Rating :
10 hp at 460/480 V AC 60 Hz for 3 phase motors
Maximum Horse Power Rating :
15 hp at 575/600 V AC 60 Hz for 3 phase motors
Maximum Horse Power Rating :
3 hp at 230/240 V AC 60 Hz for 1 phase motors
Maximum Horse Power Rating :
5 hp at 200/208 V AC 60 Hz for 3 phase motors
Maximum Horse Power Rating :
5 hp at 230/240 V AC 60 Hz for 3 phase motors
Mechanical Durability :
15 Mcycles
Mechanical Robustness :
Shocks contactor closed15 Gn for 11 ms
Mechanical Robustness :
Shocks contactor open10 Gn for 11 ms
minimum switching current :
5 mA for signalling circuit
minimum switching voltage :
17 V for signalling circuit
motor power kW :
10 kW at 500 V AC 50 Hz
motor power kW :
4 kW at 220...230 V AC 50 Hz
motor power kW :
9 kW at 415...440 V AC 50 Hz
Mounting Support :
Plate
Mounting Support :
Rail
Number of Units in Package 2 :
6
Number of Units in Package 3 :
96
Operating Altitude :
0...9842.52 ft (0...3000 m)
Operating Time :
12...22 ms closing
Operating Time :
4...19 ms opening
Overvoltage Category :
III
Package 2 GTIN :
43389110386415
Package 2 Height :
5.91 in (15.000 cm)
Package 2 Length :
15.75 in (40.000 cm)
Package 2 Weight :
11.744 lb(US) (5.327 kg)
Package 2 width :
11.81 in (30.000 cm)
Package 3 Height :
29.53 in (75.000 cm)
Package 3 Length :
23.62 in (60.000 cm)
Package 3 Weight :
206.644 lb(US) (93.732 kg)
Package 3 width :
31.50 in (80.000 cm)
Packaging made with recycled cardboard :
Yes
Packaging without single use plastic :
Yes
pole contact composition :
3 NO
Pollution Degree :
3
power dissipation per pole :
0.8 W AC-3
power dissipation per pole :
2.5 W AC-1
Product Certifications :
BV
Product Certifications :
CCC
Product Certifications :
CSA
Product Certifications :
DNV
Product Certifications :
GL
Product Certifications :
GOST
Product Certifications :
LROS (Lloyds register of shipping)
Product Certifications :
RINA
Product Certifications :
UKCA
Product Certifications :
UL
Product Name :
TeSys Deca
Product Or Component Type :
Reversing contactor
protective cover :
With
Protective Treatment :
TH IEC 60068-2-30
PVC free :
Yes
Range :
TeSys
Range :
TeSys Deca
REACh free of SVHC :
Yes
signalling circuit frequency :
25...400 Hz
Standards :
CSA C22.2 No 14
Standards :
EN 60947-4-1
Standards :
EN 60947-5-1
Standards :
IEC 60335-1
Standards :
IEC 60947-4-1
Standards :
IEC 60947-5-1
Standards :
UL 508
Sustainable packaging :
Yes
Take-back :
No
Toxic heavy metal free :
Yes
Type Of Network :
3P
Unit Type of Package 2 :
S02
Unit Type of Package 3 :
P06
UNSPSC Classification v19 :
39121529
UNSPSC Classification v23 :
39121529
utilisation category :
AC-1
utilisation category :
AC-3
Volume of Package 2 :
18000.000 cm3
Volume of Package 3 :
360000.000 cm3
Warranty :
18 months
Width :
3.5 in (90 mm)