Overview
These stand-alone Carbon Dioxide (CO2) Sensors and Controllers are used for determining ventilation necessity with HVAC controllers and to manage the amount of fresh outdoor air supplied to maintain acceptable levels of CO2 in the space.
Features
Models available with LCD that provides sensor readings and status information.Non-Dispersion-Infrared (NDIR) technology used to measure carbon dioxide gas.C7232 provides voltage or current output based on CO2 levels.SPST relay output.Used for CO2 based ventilation control (Demand Control Ventilation (DCV)).Automatic Background Calibration (ABC) algorithm based on long-term evaluation reduces required typical zero-drift check maintenance.
- Application : Carbon Dioxide Sensor
- Dimensions (mm) : 142 mm high x 84 mm wide x 87 mm deep x plus 203 mm sensing tube
- Includes : Honeywell Logo
- Comments : NEMA 3 Case
- Item Type : Product
- Mounting : Duct mount
- Frequency : 50 Hz, 60 Hz
- Approvals, Underwriters Laboratories Inc. : UL Listed, File No. E4436
- Electrical Connections : Six leadwires, 20-gauge, 6 in. long
- Operating Humidity Range (% RH) : 0 to 95% RH (non-condensing)
- Sensor : Non-dispersive Infrared (NDIR)
- Contact Ratings : 1 A @ 50 Vac/24 Vdc
- Voltage : 24 Vac/dc ±20%,
- Operating Temperature Range (F) : 32 F to 122 F
- Operating Temperature Range (C) : 0 C to 50 C
- Relay Outputs : One: Normally Open SPST
- Timing : Response--1 minute
- Accuracy : 5% full scale
- Display : Yes
- Sensor Range : 0 to 2000 ppm, adjustable
- Analog Current Output : 0/2 - 10 Vdc or 0/4 - 20 mA selectable, w/ one relay output