The C7232 Sensor and Controller is a stand-alone carbon dioxide (CO2) sensor for use in determining ventilation necessity with HVAC controllers. The C7232 measures the CO2 concentration in the ventilated space or duct. The C7232 is used in ventilation a"|CO2 Sensor: Duct-Mount: 0/2 to 10V DC or 0/4 to 20mA
- Response Time : 1min; 1min
- Analog Outputs : 2 to 10V DC
- Minimum Operating Pressure : 0.145038psi; 1kPa
- Minimum Operating Ambient Temperature : 0degree Celsius; 32degree Fahrenheit
- Mounting Type : Ductinch
- Number of Relay Outputs : 1
- Gases Detected : CO2
- Maximum Operating Ambient Temperature : 50degree Celsius; 122degree Fahrenheit
- Maximum Storage Temperature : 158°F; 70°C
- Detection Method : Non-Dispersive Infrared Absorption sensing method
- Overall Depth : 46mm; 1.81102362204724in
- Overall Width : 84mm; 3.30708661417323in
- Maximum Input Power : 24V AC/DC; 24V AC/DC
- Supply Voltage : 24V DC; 24V DC
- For Use With : Carbon Dioxide Sensor
- Minimum Storage Temperature : -4°F; -20°C
- Sensor Element : Non-dispersive Infrared (NDIR)
- Overall Height : 5.59055118110236in; 142mm
- Alarm Relay Output : 4 to 20mA
- Supply Voltage Frequency : 50/60Hz
- CO2 Sensor Range : 0 to 2000- adjustableppm
- Control System Type : Electric
- Temperature Sensor Output : 60Hz
- Display Type : No
- Operating Temperature : 0 to +50°C; 32 to +122°F
- Certificates and Standards : CE Underwriters Laboratories Inc. Listed File No. E4436 cUL UL94-5V NEMA3
- Maximum Operating Ambient Temperature : 50°C; 122°F
- Minimum Operating Ambient Temperature : 32°F; 0°C