Overview
Depending on the model, current is converted into a linear and proportional output signal of 0-5 Vdc, 0-10 Vdc or 4-20 mA and monitored by a building management controller. Use these current sensors in load trending (current monitoring) applications.
Features
Solid or split core loop-powered current transmitters for 4-20 mA modelsSolid or split core 0-5 or 0-10 Vdc modelsFast response timeIntegral DIN rail mounting flangeEasy wiring, polarity sensitive outputAccepts up to a 350 MCM (17.3 mm) cableOperates up to 250 continuous ampsTrue RMS versions are availableRoHS and WEEE ComplaintLimited 5 Year Warranty
- Dimensions (in.) : 2 45/64 in. high x 3 21/64 in. wide x 1 5/64 in. deep
- Dimensions (mm) : 69 mm high x 85 mm wide x 25 mm deep
- Weight (lb) : 0.24 lb
- Weight (kg) : 0.1 kg
- Frequency : 30 Hz to 1 kHz
- Approvals, Underwriters Laboratories Inc. : Approved
- Operating Humidity Range (% RH) : 0 to 95% RH, non-condensing
- Supply Voltage : 12 to 30 Vdc
- Operating Temperature Range (F) : 5 F to 104 F
- Operating Temperature Range (C) : -15 C to 40 C
- Approvals, CE : Pending
- Enclosure : UL94-5V/Burgundy
- Accuracy : ±0.5%
- Core Type : Split
- Supply Current : 36 mA max
- Jumper Settings : Low, Middle, High
- Output Switch Rating : 4-20 mA Average True RMS
- Isolation Voltage : 2200 Vac
- Maximum Load Resistance : 650 Ohms @ 24 Vdc (Vs-10)/0.02-40.2
- Response Time : <,200 mS
- Aperture Size : 3/4 in. (19 mm). Accepts up to 350 MCM (17.3 mm) cables.
- Approvals, Environmental Compliance : RoHS-Directive 2002/95/EC, WEEE-Directive 2002/96/EC
- Current Ratings : 0-50 Amps, 0-20 Amps, 0-10 Amps
- DIN Rail Size (in.) : 1-3/8 in.
- DIN Rail Size (mm) : 35 mm