Current Switch:
- Adjustable Trip Point
- 0.5-175 Amperage Range
- Normally Open 1.0A@30VAC/DC
- 0.5A or less Minimum Trip Point
- Split-Core Housing
- LED Status Indicator
- Sensor Power Induced from monitored conductor
- Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
- Frequency Range 50/60 hz
- Temperature Range -15 deg. to 60 deg. C (5 deg. to 140 deg. F)
- Humidity Range 10-90% RH, non-condensing
- Hysteresis 10% (typical)
- Terminal Block Maximum Wire Size 14 AWG
- Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
- Agency Approvals UL 508 open device listing CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Brand: Schneider Electric
SKU: H608
Product Literature: