Multi 9 - C60H-DC, Miniature circuit-breaker, 2P, 40 A, C Curve, 500 V DC, 10 kA
- [Ics] rated service breaking capacity : 15 kA 75 % EN/IEC 60947-2 - 220 V DC~~
- [Ics] rated service breaking capacity : 15 kA 75 % GB 14048.2 - 220 V DC
- [Ics] rated service breaking capacity : 4.5 kA 75 % EN/IEC 60947-2 - 500 V DC
- [Ics] rated service breaking capacity : 4.5 kA 75 % GB 14048.2 - 500 V DC
- [Ics] rated service breaking capacity : 7.5 kA 75 % EN/IEC 60947-2 - 440 V DC
- [Ics] rated service breaking capacity : 7.5 kA 75 % GB 14048.2 - 440 V DC
- [Ue] rated operational voltage : 220 V DC
- [Ue] rated operational voltage : 440 V DC
- [Ue] rated operational voltage : 500 V DC
- [Ui] rated insulation voltage : 500 V DC EN/IEC 60947-2
- [Uimp] rated impulse withstand voltage : 6 kVEN/IEC 60947-2
- 9 mm pitches : 4
- Ambient Air Temperature For Operation : -13…158 °F (-25…70 °C)
- Application : Distribution
- Brand : Schneider Electric
- breaking capacity : 10 kA Icu 440 V DC EN/IEC 60947-2
- breaking capacity : 10 kA Icu 440 V DC GB 14048.2
- breaking capacity : 20 kA Icu 220 V DC EN/IEC 60947-2
- breaking capacity : 20 kA Icu 220 V DC GB 14048.2
- breaking capacity : 5 kA AIR 12...500 V DC UL 1077
- breaking capacity : 6 kA Icu 500 V DC EN/IEC 60947-2
- breaking capacity : 6 kA Icu 500 V DC GB 14048.2
- Breaking capacity code : H
- By Schneider : Yes
- Carbon footprint (kg CO2 eq, Total Life cycle) : 26
- Circularity Profile : No need of specific recycling operations
- Color : Gray
- connection pitch : 0.7 in (18 mm) between phases
- Connections - Terminals : Tunnel type terminal top or bottom) - 2 0.002…0.02 in² (1…16 mm²) AWG 18...AWG 6) - flexible
- Connections - Terminals : Tunnel type terminal top or bottom) - 2 0.002…0.02 in² (1…16 mm²) AWG 18...AWG 6) - rigid stranded
- Connections - Terminals : Tunnel type terminal top or bottom) - 3 0.006 in² (4 mm²) AWG 6) - flexible stranded
- Connections - Terminals : Tunnel type terminal top or bottom) 0.002…0.04 in² (1…25 mm²) AWG 18...AWG 4) - flexible
- Connections - Terminals : Tunnel type terminal top or bottom) 0.002…0.05 in² (1…35 mm²) AWG 18...AWG 2) - rigid stranded
- contact position indicator : Yes
- curve code : C
- Depth : 2.9 in (73 mm)
- Device Short Name : C60H-DC
- earth-leakage protection : Without
- Electrical Durability : 3000 cycles 250 V DC L/R = 2 ms
- Electrical Durability : 6000 cycles 250 V DC
- Final Result for Connectable : Connectable with upgrade
- Final Result for Flywheel performance tracking : Connectable products
- Global Keywords : Breaking capacity
- Global Keywords : C60h
- Global Keywords : Direct current
- Global Keywords : Earth leakage
- Global Keywords : Electrical protection
- Global Keywords : Electrical threats
- Global Keywords : Mcb
- Global Keywords : Miniature circuit breaker
- Global Keywords : Multi9 c60hdc
- Global Keywords : Overload
- Global Keywords : Protecting equipment
- Global Keywords : Protecting people
- Global Keywords : Short circuit
- Global warming ; Total life cycle? : 26 kg CO2 eq.
- Heat Dissipation : 8.6 W 440 V - 40 A
- Height : 3.2 in (81 mm)
- IP Degree of Protection : IP20 conforming to IEC 60529
- IP Degree of Protection : IP40 (modular enclosure) conforming to IEC 60529
- Line Rated Current : 40 A 77 °F (25 °C) EN/IEC 60947-2
- Local Signalling : ON/OFF indication
- magnetic tripping limit : 7...10 x In DC
- Manufacturer : Schneider Electric
- Mechanical Durability : 20000 cycles
- Mounting Mode : Clip-on
- Mounting Support : DIN rail
- Net Weight : 0.282 lb(US) (0.128 kg)
- Network Type : DC
- number of protected poles : 2
- Number of Units in Package 2 : 6
- Number of Units in Package 3 : 72
- Override : Toggle
- Package 2 GTIN : 13606480741842
- Package 2 Height : 3.23 in (8.200 cm)
- Package 2 Length : 8.86 in (22.500 cm)
- Package 2 Weight : 3.305 lb(US) (1.499 kg)
- Package 2 width : 3.54 in (9.000 cm)
- Package 3 GTIN : 43606480741843
- Package 3 Height : 11.81 in (30.000 cm)
- Package 3 Length : 15.75 in (40.000 cm)
- Package 3 Weight : 41.021 lb(US) (18.607 kg)
- Package 3 width : 11.81 in (30.000 cm)
- Packaging made with recycled cardboard : No
- Packaging without single use plastic : No
- Pollution Degree : 3 EN/IEC 60947-2
- Power losses per pole : 4.3 W
- Product Certifications : CCC
- Product Certifications : IEC
- Product Certifications : UR
- Product Name : Multi9 C60H-DC
- Product Or Component Type : Miniature circuit-breaker
- provision for padlocking : Padlockable
- Range : Multi9
- REACh free of SVHC : Yes
- Relative Humidity : 95 % 131 °F (55 °C)
- Standards : EN/IEC 60947-2
- Standards : GB 14048.2
- Standards : UL 1077
- suitability for isolation : Yes EN/IEC 60947-2
- Take-back : No
- Temperature Shipping and Storage Range : -40…185 °F (-40…85 °C)
- Tightening Torque : 31.0 lbf.in (3.5 N.m) top or bottom
- Total power losses : 8.6 W
- Toxic heavy metal free : Yes
- Trip Unit Technology : Thermal-magnetic
- tropicalisation : 2 GB 14048.2
- tropicalisation : 2 IEC 60068-2
- Type Of Network : 2P
- Unit Type of Package 2 : BB1
- Unit Type of Package 3 : S03
- UNSPSC Classification v19 : 39121603
- UNSPSC Classification v23 : 39121603
- utilisation category : Category A EN/IEC 60947-2
- Volume of Package 2 : 1660.500 cm3
- Volume of Package 3 : 36000.000 cm3
- Width : 1.4 in (36 mm)
- Wire Stripping Length : 0.6 in (14 mm) for top or bottom connection