Overview
Pneumatic-electric switches convert a controller's pneumatic signal to electrical switching, providing start and stop control. Replacements available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/ electric switches.
Features
Models available for surface or panel mounting.Barb protected by open cage.All ferrous parts plated to prevent corrosion.Factory calibrated setpoint field adjustable to meet job requirements.Neoprene diaphragm element.
- Application : Pneumatic / Electric Switch
- Dimensions (in.) : 3 1/4 in. high x 2 7/8 in. wide x 1 3/4 in. deep
- Dimensions (mm) : 83 mm high x 73 mm wide x 44 mm deep
- Maximum Safe Operating Pressure (psi) : 30 psi, maximum
- Maximum Safe Operating Pressure (kPa) : 207 kPa, maximum
- Temperature Range (F) : 40 F to 140 F
- Temperature Range (C) : 4 C to 60 C
- Comments : No Factory Calibration
- Mounting : Panel mount
- Frequency : 60 Hz
- Approvals, Underwriters Laboratories Inc. : Category SDFY or SDFY2
- Electrical Connections : 1/4 in. quick-connect male terminals
- Operating Humidity Range (% RH) : 5 to 95% RH, 80 F (27C) max wet bulb
- Approvals, Canadian Underwriters Laboratories Inc. : Listed, Volume I
- Differential Pressure Range (psi) : 1 psi
- Differential Pressure Range (kPa) : 7 kPa
- Switch Operation : Converts pneumatic signal to electrical switching action (SPDT)
- Pilot Duty Ratings : 720 VA @ 125, 250 or 277 Vac
- Switch Type : Pneumatic/Electric Switch
- Air connections : Barb fitting for 1/4 in. (6 mm) O.D. plastic tubing
- Setpoint Range (psi) : Field Adjustable--2 to 17 psi
- Setpoint Range (kPa) : Field Adjustable--14 to 117 kPa
- Motor Load : 3/4 hp @ 125, 250 or 277 Vac
- Resistive Load : 25A @ 125, 250 or 277 Vac, 10A @ 480 Vac