An E/P Transducer accepts a proportional voltage signal from an electronic controller and converts it into a proportional pneumatic signal of 0.2 to 1.0 bar to operate pneumatic actuators or reset pneumatic controllers. The RP7517A accepts a 2...10 Vdc"|Electronic Pneumatic Transducer: 24V AC External Transformer: 2 7/16in Wide: 3 5/8in High: 2in Deep
- Application : Electric to pneumatic Transducer
- Airflow Usage : 0.025 scfm (117mL/s)
- Dimensions (in.) : 2 7/16 in. wide x 3 5/8 in. high x 2 in. deep
- Dimensions (mm) : 62 mm wide x 92 mm high x 52 mm deep
- Maximum Safe Operating Pressure (psi) : 30 psi, maximum
- Maximum Safe Operating Pressure (kPa) : 205 kPa, maximum
- Temperature Range (F) : 131 F, maximum
- Temperature Range (C) : 55 C, maximum
- Electrical Connections : 30 in. (762 mm) lead wire
- Operating Humidity Range (% RH) : 5 to 95% RH
- Voltage : 24 Vac external transformer
- Pressure Range (psi) : 0 to 18 psi, Output--3 to 15 psi
- Pressure Range (kPa) : 0 to 125 kPa, Output--21 to 103 kPa
- Input Signal : 2 to 10 Vdc at 0.1 mA max
- Air connections : Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing
- Capacity : 0.45 scfm (211 mL/s)
- Nominal High End (psi) : 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc ( min. )
- Nominal High End (kPa) : 116 kPa with 125 kPa main pressure at 12 Vdc or 110 kPa at 11 Vdc ( min. )
- Nominal Low End (psi) : 0.5 psi at 0 Vdc
- Nominal Low End (kPa) : 3.5 kPa at 0 Vdc
- Current : 16 mA