TeSys D Contactor |Number of Poles: 3-Poles|Pole Contact Composition: 3 NO|Rated Operational Current: 80A|Control Circuit Voltage: 120V AC 50/60 Hz|Non-Reversing
- [Icw] rated short-time withstand current : 100 A - 1 s for signalling circuit~~
- [Icw] rated short-time withstand current : 120 A - 500 ms for signalling circuit
- [Icw] rated short-time withstand current : 135 A 104 °F (40 °C) - 10 min for power circuit
- [Icw] rated short-time withstand current : 140 A - 100 ms for signalling circuit
- [Icw] rated short-time withstand current : 320 A 104 °F (40 °C) - 1 min for power circuit
- [Icw] rated short-time withstand current : 640 A 104 °F (40 °C) - 10 s for power circuit
- [Icw] rated short-time withstand current : 990 A 104 °F (40 °C) - 1 s for power circuit
- [Ie] rated operational current : 125 A (at
- [Ie] rated operational current : 80 A (at
- [Ith] conventional free air thermal current : 10 A (at 140 °F (60 °C)) for signalling circuit
- [Ith] conventional free air thermal current : 125 A (at 140 °F (60 °C)) for power circuit
- [Uc] control circuit voltage : 120 V AC 50/60 Hz
- [Ue] rated operational voltage : Power circuit
- [Ui] rated insulation voltage : Power circuit 1000 V IEC 60947-4-1
- [Ui] rated insulation voltage : Power circuit 600 V CSA
- [Ui] rated insulation voltage : Power circuit 600 V UL
- [Ui] rated insulation voltage : Signalling circuit 600 V CSA
- [Ui] rated insulation voltage : Signalling circuit 600 V UL
- [Ui] rated insulation voltage : Signalling circuit 690 V IEC 60947-1
- [Uimp] rated impulse withstand voltage : 8 kV IEC 60947
- Associated Fuse Rating : 10 A gG for signalling circuit conforming to IEC 60947-5-1
- Associated Fuse Rating : 160 A gG at
- Associated Fuse Rating : 200 A gG at
- auxiliary contact composition : 1 NO + 1 NC
- auxiliary contacts type : Mechanically linked 1 NO + 1 NC IEC 60947-5-1
- auxiliary contacts type : Mirror contact 1 NC IEC 60947-4-1
- average impedance : 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- Brand : Schneider Electric
- By Schneider : Yes
- Carbon footprint (kg CO2 eq, Total Life cycle) : 59
- Circularity Profile : No need of specific recycling operations
- climatic withstand : IACS E10 exposure to damp heat
- coil technology : Without built-in suppressor module
- Connections - Terminals : Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible with cable end
- Connections - Terminals : Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible without cable end
- Connections - Terminals : Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: solid without cable end
- Connections - Terminals : Power circuit: connector 2 0.006…0.02 in² (4…16 mm²) - cable stiffness: flexible with cable end
- Connections - Terminals : Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: flexible without cable end
- Connections - Terminals : Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: solid without cable end
- contact compatibility : M11
- contactor application : Motor control
- contactor application : Resistive load
- control circuit type : AC 50/60 Hz
- control circuit voltage limits : 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
- control circuit voltage limits : 0.8...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 50 Hz
- control circuit voltage limits : 0.85...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 60 Hz
- control circuit voltage limits : 1...1.1 Uc (131…158 °F (55…70 °C)):operational AC 50/60 Hz
- Depth : 5.1 in (130 mm)
- Device Short Name : LC1D
- Electrical Durability : 0.8 Mcycles 125 A AC-1
- Electrical Durability : 1.5 Mcycles 80 A AC-3
- Electrical Durability : 1.5 Mcycles 80 A AC-3e
- Final Result for Flywheel performance tracking : Non Flywheel
- fire resistance : 1562 °F (850 °C) IEC 60695-2-1
- Flame Retardance : V1 conforming to UL 94
- Global Keywords : 3-pole contactor
- Global Keywords : AC coil
- Global Keywords : AC-3
- Global Keywords : Built-in auxiliary contact
- Global Keywords : LC1D
- Global Keywords : Magnetic contactor
- Global Keywords : Motor control
- Global Keywords : Motor switching
- Global Keywords : Power contactor
- Global Keywords : Screw terminals
- Global Keywords : TeSys D
- Global Keywords : TeSys Deca
- Global warming ; Total life cycle? : 59 kg CO2 eq.
- Heat Dissipation : 6…10 W at 50/60 Hz
- Height : 5 in (127 mm)
- Hold-In Power Consumption In Va : 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
- Hold-In Power Consumption In Va : 26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
- inrush power in VA : 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
- inrush power in VA : 245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
- insulation resistance : > 10 MOhm for signalling circuit
- IP Degree of Protection : IP20 front face IEC 60529
- Irms rated making capacity : 1100 A at 440 V for power circuit conforming to IEC 60947
- Irms rated making capacity : 140 A AC for signalling circuit conforming to IEC 60947-5-1
- Irms rated making capacity : 250 A DC for signalling circuit conforming to IEC 60947-5-1
- Manufacturer : Schneider Electric
- Maximum Horse Power Rating : 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- Maximum Horse Power Rating : 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors
- Maximum Horse Power Rating : 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors
- Maximum Horse Power Rating : 60 hp at 460/480 V AC 50/60 Hz for 3 phase motors
- Maximum Horse Power Rating : 60 hp at 575/600 V AC 50/60 Hz for 3 phase motors
- Maximum Horse Power Rating : 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
- maximum operating rate : 3600 cyc/h at 60 °C
- Mechanical Durability : 4 Mcycles
- Mechanical Robustness : Shocks contactor closed 10 Gn for 11 ms)
- Mechanical Robustness : Shocks contactor open 8 Gn for 11 ms)
- Mechanical Robustness : Vibrations contactor closed 3 Gn, 5...300 Hz)
- Mechanical Robustness : Vibrations contactor open 2 Gn, 5...300 Hz)
- minimum switching current : 5 mA for signalling circuit
- minimum switching voltage : 17 V for signalling circuit
- motor power kW : 15 kW at 400 V AC 50/60 Hz (AC-4)
- motor power kW : 22 kW at 220...230 V AC 50/60 Hz (AC-3)
- motor power kW : 22 kW at 220...230 V AC 50/60 Hz (AC-3e)
- motor power kW : 37 kW at 380...400 V AC 50/60 Hz (AC-3)
- motor power kW : 37 kW at 380...400 V AC 50/60 Hz (AC-3e)
- motor power kW : 45 kW at 415...440 V AC 50/60 Hz (AC-3)
- motor power kW : 45 kW at 415...440 V AC 50/60 Hz (AC-3e)
- motor power kW : 45 kW at 660...690 V AC 50/60 Hz (AC-3)
- motor power kW : 45 kW at 660...690 V AC 50/60 Hz (AC-3e)
- motor power kW : 55 kW at 500 V AC 50/60 Hz (AC-3)
- motor power kW : 55 kW at 500 V AC 50/60 Hz (AC-3e)
- Mounting Support : Plate
- Mounting Support : Rail
- Net Weight : 3.51 lb(US) (1.59 kg)
- non-overlap time : 1.5 ms on de-energisation between NC and NO contact
- non-overlap time : 1.5 ms on energisation between NC and NO contact
- Number of Units in Package 2 : 5
- Number of Units in Package 3 : 80
- Operating Altitude : 0...9842.52 ft (0...3000 m)
- Operating Time : 20...35 ms closing
- Operating Time : 6...20 ms opening
- Overvoltage Category : III
- Package 2 GTIN : 43389110440865
- Package 2 Height : 5.91 in (15.000 cm)
- Package 2 Length : 15.75 in (40.000 cm)
- Package 2 Weight : 17.800 lb(US) (8.074 kg)
- Package 2 width : 11.81 in (30.000 cm)
- Package 3 Height : 29.53 in (75.000 cm)
- Package 3 Length : 31.50 in (80.000 cm)
- Package 3 Weight : 293.524 lb(US) (133.140 kg)
- Package 3 width : 23.62 in (60.000 cm)
- Packaging made with recycled cardboard : Yes
- Packaging without single use plastic : Yes
- Permissible Ambient Air Temperature Around The Dev : 140…158 °F (60…70 °C) with derating
- Permissible Ambient Air Temperature Around The Dev : -40…140 °F (-40…60 °C)
- pole contact composition : 3 NO
- Pollution Degree : 3
- power dissipation per pole : 12.5 W AC-1
- power dissipation per pole : 5.1 W AC-3
- power dissipation per pole : 5.1 W AC-3e
- Product Certifications : CB Scheme
- Product Certifications : CCC
- Product Certifications : CE
- Product Certifications : CSA
- Product Certifications : EAC
- Product Certifications : Marine
- Product Certifications : UKCA
- Product Certifications : UL
- Product Or Component Type : Contactor
- protective cover : With
- Protective Treatment : THIEC 60068-2-30
- PVC free : Yes
- Range : TeSys
- rated breaking capacity : 1100 A at 440 V for power circuit conforming to IEC 60947
- REACh free of SVHC : Yes
- safety reliability level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
- safety reliability level : B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- signalling circuit frequency : 25...400 Hz
- Standards : CSA C22.2 No 14
- Standards : EN 60947-4-1
- Standards : EN 60947-5-1
- Standards : IEC 60335-1:Clause 30.2
- Standards : IEC 60335-2-40:Annex JJ
- Standards : IEC 60947-4-1
- Standards : IEC 60947-5-1
- Standards : UL 60335-2-40:Annex JJ
- Standards : UL 60947-4-1
- Sustainable packaging : Yes
- Take-back : No
- Tightening Torque : Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
- Tightening Torque : Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
- Tightening Torque : Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
- Tightening Torque : Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm
- Tightening Torque : Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
- Toxic heavy metal free : Yes
- Type Of Network : 3P
- Unit Type of Package 2 : S02
- Unit Type of Package 3 : P06
- UNSPSC Classification v19 : 39121529
- UNSPSC Classification v23 : 39121529
- utilisation category : AC-1
- utilisation category : AC-3
- utilisation category : AC-3e
- utilisation category : AC-4
- Volume of Package 2 : 18000.000 cm3
- Volume of Package 3 : 360000.000 cm3
- Warranty : 18 months
- Width : 3.3 in (85 mm)