Overview
The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK, and TR23-WK sensors are a family of wireless wall modules and receivers. All models report space temperature; TR23 models come with setpoint adjustment and override.
Features
Wall module to Receiver (point to point) wireless kits can replace any standard wired sensorWireless Kits (wall module and receiver) are pre bound at the factory for quick installationSignal Strength LED built into the wall moduleLow battery indicationOptional dip switches available to bind any wall module to any receiverApproximate 5 year battery life with AA Alkaline (included), 7.5 year with LithiumLocking screw discourages tampering and battery theft
- Application : Wall Module
- Includes : TR21-WSU and WRECVRU
- Item Type : Product
- Mounting : Wall mount
- Approvals, Underwriters Laboratories Inc. : Receiver: UL94-5VA, UL94 plastic enclosure
- Operating Humidity Range (% RH) : 5 to 95% RH, non-condensing
- Setpoint Temperature Range (C) : 13 C to 30 C
- Setpoint Temperature Range (F) : 55 F to 85 F
- Operating Temperature Range (F) : Sensor: 45 F to 99 F, Receiver: -40° to +150°F
- Operating Temperature Range (C) : Sensor: 7 C to 37 C, Receiver: -40° to + 65.5°C
- Shipping and Storage Temperature Range (F) : -40 F to +150 F
- Shipping and Storage Temperature Range (C) : -40° to + 65.5°C
- Approvals, Federal Communications Commission : FCC Part 15
- Accuracy (F) : ± 1 F across 53.6 F to 86 F
- Accuracy (C) : (± 0.5 C) across 12 C to 30 C
- Radio Frequency : 2.4 GHz (IEEE Std 802.15.4-2003 compliant)
- Wireless Range : Open Range--3000 feet, Typical Range--100 feet
- Output power : 16dBm