The TR40 and TR42 series of room sensors and displays are designed to operate with Honeywell controllers. All models have an integral temperature sensor and variants are available that also include sensors for relative humidity and/or CO2 concentration. Th|Wall Module: Temperature: Humidity: CO2: Sylk-Bus
- Application : Temperature, Humidity, CO2 Sensor Wall Module
- Dimensions (in.) : 3-1/4 in wide x 4-3/4 in high x 7/8 in. deep
- Comments : Configurable with Niagara Workbench
- Item Type : Product
- Mounting : Vertical Mount
- Approvals, Underwriters Laboratories Inc. : UL94-V0 plastic enclosure
- Operating Humidity Range (% RH) : 5 to 95% RH, non-condensing
- Setpoint Temperature Range (C) : Default range is 10 C to 35 C, configurable for other ranges
- Setpoint Temperature Range (F) : Default range is 55 F to 85 F, configurable for other range
- Switch Positions (Fan) : Configurable
- Operating Temperature Range (F) : 32 F to 110 F
- Operating Temperature Range (C) : 0 C to 43 C
- Shipping and Storage Temperature Range (F) : -40 F to +150 F
- Shipping and Storage Temperature Range (C) : -40 C to +65.5 C
- Approvals, Federal Communications Commission : FCC Part 15
- Approvals, CE : Approved
- Network Communications : Two-wire Sylk
- Accuracy (F) : ±0.36 F at 77 F
- Accuracy (C) : ±0.2 C at 25 C
- Color : White
- Accuracy : ±3% RH
- Password Protection : Yes