Overview
Controls heating, cooling and space demand oriented economizer operation in the Honeywell Electronic Dual Set point Multizone control system.
Features
Controls 3 stages of on/off heating, modulated heating, modulated economizer, 3 stages of on/off cooling and modulated cooling.Responds to highest heating and cooling demand signal from up to 12 T7080 Zone Thermostat/Transmitters.Analyzer is short-circuit protected source of 24 Vdc power for zone thermostat/transmitter, sensor and W7081A Limit Controller Package.Switches all stages off when power is interrupted; switches stages on when power is restored.Compressor turn-on time delays must be incorporated for each compressor.No adjustment or calibrations required.Night setback and cooling shutdown for individual or all zones by addition of time-clock.Mounts with 4 No. 8 Screws (not provided) through holes in base.
- Application : Packaged RTU, Furnace, Split System
- Dimensions (in.) : 6 1/4 in. high x 4 1/8 in. wide x 2 5/16 in. deep
- Dimensions (mm) : 159 mm high x 105 mm wide x 59 mm deep
- Frequency : 50 Hz, 60 Hz
- Approvals, Underwriters Laboratories Inc. : Component Recognized
- Approvals, Canadian Standards Association : Component Recognized
- Electrical Connections : 1/4 in. quick-connect male terminals
- Application Size : 3 Heat / 3 Cool
- Control System : W7080 control system
- Compatible With : T7080 Thermostat
- Voltage : 24 Vdc
- Operating Temperature Range (F) : -40 F to +150 F
- Operating Temperature Range (C) : -40 C to +65 C
- Shipping and Storage Temperature Range (F) : -40 F to +150 F
- Shipping and Storage Temperature Range (C) : -40 C to +65 C
- Approvals, Department of Defense Guidelines : Meets
- Approvals, ASHRAE Guidelines : Meets ASHRAE 90-75