Valve; 1/2" 2 Way, NPT, NC; 2.5 Cv; 115VAC; Fail Closed :- These globe zone control valves are designed to regulate the flow of hot or chilled water to such applications as VAV terminal unit reheat coils, fan coil units, and induction units. The compact design of these units allows easy installation within small enclosures. Valve bodies, available in 1/2 to 1"; line sizes, are all normally open. The actuator determines the fail position. Actuators have position indication and manual override. Replacement actuators can be installed on the valve bodies without tools. Features include: Choice of tri-state/floating or proportional fail-in-place or two-position (NO or NC) spring-return fail-safeCompact sizeSpring-return fail-safe actuators feature easy manual override, visual position indication, UL listing for plenum installations, and heat-resistant lead wiresNon-fail-safe actuators feature manual override (with 3 mm hex wrench), visual position indication, and are CE compliant and UL listed
- Actuator Type : Electric
- Brand : KMC Controls
- CV : 2.5
- Control Input : 120 VAC
- Fail-Safe : Yes
- Fail-Safe Type : Spring
- Input Types : Two-position
- Normality (Fail) : NC
- Power Supply : 120 VAC
- Selection Guide : Valve And Actuator
- Timing (sec) : 35
- Valve Connection : Female NPT
- Valve Piping Style : 2W
- Valve Size : 1/2"
- Valve Type : Zone