The PH Series pressure transducers are designed for steam, air, gas, and liquid pressure measurement in all media compatible with 17-4 PH stainless steel. They utilize a microprocessor controlled sensor profiled for exceptional accuracy and reliability. All models feature three switch-selectable ranges and a "test mode" to verify wiring and panel input scaling. A pushbutton and digital input terminal is used to automatically zero the output, and the microprocessor safeguards against accidental zero adjustment during operation. The field-selectable output, offering options of 0-5V, 0-10VDC, or 4-20mA, ensures excellent systems compatibility. Jumper controlled surge damping is provided on all models to prevent false alarms. Digitally Controlled Gauge| Pressure Transducer| 0-100 psig| Standard
- [Us] rated supply voltage : 24 V AC~~
- Analogue Output Type : 0...10 V DC
- Analogue Output Type : 0...5 V DC
- Analogue Output Type : 4...20 mA
- Application : Energy and Water Management
- Application : Gas Pressure
- Application : Pump and Compressor Monitoring
- Application : Refrigerant Equipment Monitoring
- Brand : Veris Industries
- Burst Pressure : 500 psig (34 bar)
- By Schneider : Yes
- Controlled Fluid : Water
- Depth : 2.2 in (56 mm)
- Final Result for Connectable : Not connectable
- Final Result for Flywheel performance tracking : Non Flywheel
- Fitting Size : 1/4" NPT
- Fitting Type : Male
- Height : 5.08 in (129 mm)
- Humidity Calibration Certificate : None
- Local Signalling : Red/green LED
- Location : Plant Room
- Manufacturer : Schneider Electric
- Material : Powder coated steel: enclosure
- Material : Stainless steel: Fitting
- Mounting Support : Panel
- Output Type : Analog
- Packaging made with recycled cardboard : No
- Packaging without single use plastic : No
- Pressure Measurement Accuracy : +/- 1 % FS
- Pressure Measurement Range : 0...100 psi (0...7 bar)
- Product Or Component Type : Sensor
- Relative Humidity : 0…90 % RH, non-condensing
- Sensor Model : PHX07S
- Take-back : No
- Temperature Ambient Operating Range : 14…131 °F (-10…55 °C)
- Type Of Measurement : Gauge Pressure
- Width : 2.2 in (56 mm)
- Wiring Technique : 3-wire