PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Ammeter with a 6.3A trip unit and an LSIG function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 100% with an ABC phase connection. This circuit breaker has a continuous current rating of 100% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Range : PowerPact
- Product name : PowerPact L
- Device short name : L-Frame
- Product or Component Type : Circuit breaker
- Device Application : Distribution
- Line Rated Current : 400 A
- Number of Poles : 3P
- control type : Toggle
- Breaking capacity code : J
- [Ue] rated operational voltage : 600 V AC 50/60 Hz IEC 60947-3
- Network Frequency : 50/60 Hz
- [Uimp] rated impulse withstand voltage : 8 kV IEC 60947-2
- Trip unit technology : Electronic, ammeter, MicroLogic 6.3 A, LSIG
- Continuous current rating : 100 %
- [Ui] rated insulation voltage : 750 V IEC 60947-2
- Trip unit name : MicroLogic 6.3 A
- Protection technology : Current limiter
- Suitability for isolation : Yes IEC 60947-2
- utilisation category : Category A
- AWG gauge : 2 x AWG 2/0...500 kcmil aluminium/copper
- Mounting mode : I-Line bracket)
- Mounting Support : Bracket
- Electrical connection : I-Line connection, line, Lugs, load
- Terminal identifier : AL600LS52K3
- Long time pick-up adjustment range : 0.25...1 x In
- mounting height : 6 in (152.40 mm)
- Tightening torque : 442.54 lbf.in (50 N.m) 0.11…0.37 in² (70…240 mm²) (AWG 2/0...500 kcmil)
- Power wire stripping length : 1.22 in (31 mm), 2.40 in (61 mm)
- Color : Black
- Height : 13.39 in (340 mm)
- Width : 5.51 in (140 mm)
- Depth : 4.33 in (110 mm)
- Net Weight : 13.67 lb(US) (6.2 kg)
- Phase connection : ABC
- communication interface : Modbus, Ethernet
- circuit breaker application : HACR rated
- Standards : UL, CSA, NEMA, NOM-003-SCFI-2000, IEC 60947-2
- Product certifications : UL, CSA, NOM
- IP degree of protection : Front cover IP40
- Pollution degree : 3 IEC 60947-1
- Ambient Air Temperature for Operation : -13…158 °F (-25…70 °C)
- Ambient Air Temperature for Storage : -58…185 °F (-50…85 °C)
- Operating altitude : < 6561.68 ft (2000 m) without derating, 5000 m with derating
- Category : US10DE201118
- Discount Schedule : 0DE2
- Returnability : Yes
- Country of origin : US
- Unit Type of Package 1 : PCE
- Number of Units in Package 1 : 1
- Package 1 Height : 14.69 in (37.3 cm)
- Package 1 Width : 5.94 in (15.1 cm)
- Package 1 Length : 6.61 in (16.8 cm)
- Package 1 Weight : 17.00 lb(US) (7.711 kg)
- Warranty : 18 months