- [Ith] conventional free air thermal current : 5 A signalling circuit~~
- [Ue] rated operational voltage : 690 V AC 0...400 Hz power circuit IEC 60947-4-1
- [Ui] rated insulation voltage : Power circuit 600 V CSA
- [Ui] rated insulation voltage : Power circuit 600 V UL
- [Ui] rated insulation voltage : Power circuit 690 V IEC 60947-4-1
- [Uimp] rated impulse withstand voltage : 6 kV
- Ambient Air Temperature For Operation : -4…140 °F (-20…60 °C) without derating IEC 60947-4-1
- Associated Fuse Rating : 4 A BS for signalling circuit
- Associated Fuse Rating : 4 A gG for signalling circuit
- auxiliary contact composition : 1 NO + 1 NC
- Brand : Schneider Electric
- By Schneider : Yes
- Carbon footprint (kg CO2 eq, Total Life cycle) : 4
- climatic withstand : IACS E10
- Connections - Terminals : Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) flexible with cable end
- Connections - Terminals : Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) flexible without cable end
- Connections - Terminals : Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) solid without cable end
- Connections - Terminals : Power circuit EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) flexible with cable end
- Connections - Terminals : Power circuit EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) flexible without cable end
- Connections - Terminals : Power circuit EverLink BTR screw connectors 1 0.002…0.05 in² (1…35 mm²) solid without cable end
- Control Type : Blue push-button reset
- Control Type : Red push-button stop
- Depth : 4.8 in (123 mm)
- Device Short Name : LRD
- dielectric strength : 1.89 kV 50 Hz IEC 60947-1
- Final Result for Flywheel performance tracking : Non Flywheel
- Flame Retardance : V1 conforming to UL 94
- Global Keywords : 37-50 A
- Global Keywords : Class 10A
- Global Keywords : LRD
- Global Keywords : Motor protection
- Global Keywords : TeSys D
- Global Keywords : TeSys LRD
- Global Keywords : Thermal overload relays
- Global Keywords : Thermal protection
- Global warming ; Total life cycle? : 4 kg CO2 eq.
- Height : 2.8 in (70 mm)
- IP Degree of Protection : IP20 conforming to IEC 60529
- Manufacturer : Schneider Electric
- Mechanical Robustness : Shocks15 Gn for 11 ms IEC 60068-2-7
- Mechanical Robustness : Vibrations4 gn IEC 60068-2-6
- Mounting Support : Plate, with specific accessories
- Mounting Support : Rail, with specific accessories
- Mounting Support : Under contactor
- Net Weight : 0.827 lb(US) (0.375 kg)
- Network Frequency : 0...400 Hz
- Network Type : AC
- Network Type : DC
- Number of Units in Package 2 : 13
- Number of Units in Package 3 : 208
- Package 2 GTIN : 43389119215501
- Package 2 Height : 5.91 in (15.0 cm)
- Package 2 Length : 15.75 in (40.0 cm)
- Package 2 Weight : 12.134 lb(US) (5.504 kg)
- Package 2 width : 11.81 in (30.0 cm)
- Package 3 Height : 30.31 in (77.0 cm)
- Package 3 Length : 23.62 in (60.0 cm)
- Package 3 Weight : 212.887 lb(US) (96.564 kg)
- Package 3 width : 31.50 in (80.0 cm)
- Packaging made with recycled cardboard : Yes
- Packaging without single use plastic : Yes
- permissible current : 0.06 A 440 V DC-13 signalling circuit
- permissible current : 0.95 A 380 V AC-15 signalling circuit
- phase failure sensitivity : Tripping current 130 % of Ir on two phase, the last one at 0
- Product Certifications : ATEX INERIS
- Product Certifications : CCC
- Product Certifications : CSA
- Product Certifications : DNV-GL
- Product Certifications : EAC
- Product Certifications : EU-RO MR
- Product Certifications : IEC
- Product Certifications : LROS (Lloyds register of shipping)
- Product Certifications : RMRS
- Product Certifications : UKCA
- Product Certifications : UL
- Product Compatibility : LC1D40A
- Product Compatibility : LC1D50A
- Product Compatibility : LC1D65A
- Product Name : TeSys Deca
- Product Name : TeSys LRD
- Product Or Component Type : Differential thermal overload relay
- Range : TeSys
- Range : TeSys Deca
- REACh free of SVHC : Yes
- relay application : Motor protection
- Standards : CSA C22.2 No 60947-4-1
- Standards : CSA C22.2 No 60947-5-1
- Standards : EN 50495
- Standards : EN/IEC 60947-4-1
- Standards : EN/IEC 60947-5-1
- Standards : UL 60947-4-1
- Standards : UL 60947-5-1
- Sustainable packaging : Yes
- Take-back : No
- temperature compensation : -4…140 °F (-20…60 °C)
- Temperature Shipping and Storage Range : -76…158 °F (-60…70 °C)
- thermal overload class : Class 10A IEC 60947-4-1
- thermal protection adjustment range : 37…50 A
- Tightening Torque : Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals
- Tightening Torque : Power circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors
- Toxic heavy metal free : Yes
- tripping threshold : 1.14 +/- 0.06 Ir IEC 60947-4-1
- Unit Type of Package 2 : S02
- Unit Type of Package 3 : P06
- UNSPSC Classification v19 : 39122330
- UNSPSC Classification v23 : 39122330
- Volume of Package 2 : 18000.0 cm3
- Volume of Package 3 : 369600.0 cm3
- Warranty : 18 months
- Width : 2.2 in (55 mm)