QFA32SS.FWSN - Room Unit, RH&T, Full HMI, 0-10V / 4-20mA Outputs
- Measurement range humidity : 10…90 % r.h.
- Operating voltage : 18 to 36 Vdc or 24 Vac ± 20 %
- Analog outputs : 0-10V / 4-20mA (selectable)
- Measuring range : Temperature: 32 to 122°F; Humidity: 10 to 90% RH
- Measurement accuracy : Temperature: +/- 0.4°F @ 32 °F, Humidity: +/-5% between 10 to 90% r.h.
- Display : Full HMI
- Dimensions (W x H x D) : 5.25 x 3 x 3.75 in