VT8650 Series room controllers are used for Roof Top Unit control. |It is IP ready and can take a WIFI Module. |The room controllers rated supply voltage range is 24 V AC at 50 or 60 Hz +/-15 %. |The rated current is 4A. |The device consumption is up to 12 VA. |The room controller is colored white and is equiped with a communication port that uses BACnet MS/TP protocol and PIR and RH sensors. |Its Room and Outdoor Air Temperature Display Range is between -40 and 122 oC. |The measurement accuracy is +/- 0.5 %. |The temperature setting range is 54 to 100 oC for cooling and 54 to 100 oC for heating. |The room controller is equiped with 2 digital inputs, 5 analog inputs (5 to 10 V), 4 analog outputs, and 5 digital outputs. |The analog output voltage is 0 to 10 V DC at 2 kOhm resistance. |The digital output rating is 28 V AC 50 or 60 Hz, 0.3 A, 1.5 A inrush current. |The product follows the following standards: IEC 61326-1: 2005, FCC part 15 subpart C, RSS 210 issue 8, FCC part 15 subpart B, ICES-003, EN 60950-1: 2006/A2, EN 60950-1: 2013, ETSI EN 301 489-1: v1.9.2. |The product follows the directives: 2014/30/EU - electromagnetic compatibility, 2014/35/EU - low voltage directive, 2014/53/EU - radio equipment directive. |The ambient air temperature for operation is between 32 and 122 oC. |The relative humidity for operating or storage is between 0 and 75 % non condensing. |The humidity reading range is 10 to 90 % RH non-condensing.
- [Us] rated supply voltage : 24 V AC 50/60 Hz +/- 15 %~~
- Application : Staging equipment (RTU/HP)
- AWG Gauge : AWG 22...AWG 18
- Brand : Viconics
- By Schneider : Yes
- Carbon footprint (kg CO2 eq, Total Life cycle) : 181
- Color Casing : White
- Communication Port Protocol : BACnet MS/TP
- Communication Port Protocol : Modbus RTU
- Communication Port Protocol : Zigbee
- Depth : 1.0 in (25 mm)
- Device Short Name : SE8600
- Directives : 2014/30/EU - electromagnetic compatibility
- Directives : 2014/35/EU - low voltage directive
- Directives : 2014/53/EU - radio equipment directive
- Economizer : No
- Final Result for Connectable : Connectable ready
- Final Result for Flywheel performance tracking : Edge control
- Function Available : Available with CO2/RH/T
- Function Available : Brightness sensor
- Function Available : Changes can be made directly over display
- Function Available : Code lock function
- Function Available : Easily configurable
- Function Available : Fan control
- Function Available : Firmware update by USB
- Function Available : HVAC control
- Global warming ; Total life cycle? : 181 kg CO2 eq.
- Height : 4.7 in (120 mm)
- Humidity Calibration Certificate : 1 pt
- Humidity Control : Yes
- Humidity Measurement Drift : Less Than 1 % Yearly
- Humidity Setting Range : 30…95 %
- Indivisible Sale Qty : 1
- Information Displayed : Temperature - 40...122 °F
- Input Type : 2
- Input Type : Analog 5
- Input Type : Discrete 2
- Input Type : Dry contact 2
- Input Voltage : 0...10 V
- Market Segment : Edificios
- Market Segment : Lodging/Hotel
- Market Segment : Non-critical buildings
- Market Segment : Office
- Market Segment : Residential
- Market Segment : Sanidad
- Market Segment : School
- Market Segment : Small commercial
- Measurement Accuracy : Humidity +/- 5 %, 20...80 % RH non-condensing)
- Measurement Accuracy : Temperature +/- 0.5 °C
- Net Weight : 12.0 oz (340 g)
- Network Frequency : 50 Hz
- Network Frequency : 60 Hz
- Output Current : 0.3 A universal output
- Output Current : 1 A relay output
- Output Current : 1.5 A universal output inrush)
- Output Current : 3 A relay output inrush)
- Output Type : 4 xanalog
- Output Type : 4 xuniversal
- Output Type : 5 xdiscrete
- Output Type : 5 xrelay output
- Output Voltage : 0...10 V AC/DC voltage output
- Output Voltage : 0...10 V DC analog output
- Output Voltage : 24 V AC/DC relay output
- Packaging made with recycled cardboard : No
- Packaging without single use plastic : Yes
- PIR Cover : Yes
- Product Name : SE8000 Series
- Product Or Component Type : Roof top unit
- Range : EcoStruxure Building Expert
- Relative Humidity : 0…75 %
- Scheduling : Yes
- SCIP Number : 36265055-6713-4452-af94-2e6566ec0ebd
- Sensor Type : 10 kOhm T2 NTC thermistor Temperature
- Sensor Type : Single point calibrated bulk polymer RH sensor Humidity
- Sensor Type : Space RH sensor Humidity
- Standards : CSA E60730-2-9
- Standards : EN/IEC 60730-1
- Standards : EN/IEC 60730-2-13
- Standards : EN/IEC 60730-2-9
- Standards : ETSI EN 300 328:v2.1.1
- Standards : ETSI EN 301 489-1:v1.9.2
- Standards : ETSI EN 301 489-17:v2.2.1, 2012
- Standards : FCC part 15 subpart B
- Standards : FCC part 15 subpart C
- Standards : ICES-003
- Standards : RSS 247
- Standards : UL 60730-2-13
- Standards : UL 60730-2-9
- Surface Finish : Matte
- Surface Treatment : Untreated
- Take-back : No
- Temperature Ambient Operating Range : 32…122 °F (0…50 °C)
- Temperature Resolution : 0.1 °C
- Temperature Setting Range : 40…90 °F (4.5…32 °C) heating
- Temperature Setting Range : 54…100 °F (12…37.5 °C) cooling
- Temperature Shipping and Storage Range : -22…122 °F (-30…50 °C)
- Width : 3.4 in (86 mm)